Calibrating Your Module

Chapter 6

6-3

Nulling the Input Offset

After completing the 10V reference adjustment, turn off power to your
processor and I/O chassis and complete the following steps.

1. Move jumper E1 (Figure 6.1) from the default position (connecting

the center and right posts) to the calibration position (connecting the
center and left posts).

2. Attach the negative lead of your voltmeter to an analog common (pin

5, 10, 15, 20 or 21) of the field wiring arm.

3. Attach the positive lead of your voltmeter to TP2.

4. Turn on power to your processor and I/O chassis. Check to make

sure the red FLT indicator is lit and the green RUN indicator is off. If
the red indicator is off, check the position of E1.

5. Adjust potentiometer R63 (Figure 6.1) until the value at

TP2 = 0.0000V (+0.0002V maximum).

6. After completing the adjustment, remove power from the I/O chassis

and return jumper E1 to the default position.

In this chapter you learned how to calibrate your module. This included the
necessary tools, adjusting the 10V reference, and nulling the offset.

Chapter Summary