Module Configuration

Chapter 4

4-3

You can select single-ended or differential inputs using the designated bit
in the configuration file. Inputs to a particular module must be all
single-ended or all differential. Set BTW word 3, bit 08 (bit 10 octal) as
shown in Table 4.C.

Table 4.C

Selecting SingleĆended or Differential Inputs

Decimal Bit 8

(Octal Bit 10)

Input type

1

differential inputs

0

singleĆended inputs

You must also indicate what format will be used to read data from your
module. Typically, you select BCD with PLC-2 processors, and 2’s
complement binary with PLC-3 and PLC-5 processors. See Appendix C
for details on data format. You use BTW word 3 bits 09-10 (11-12 octal) to
set the data format (Table 4.D).

Table 4.D

Selecting the Data Format

Decimal Bit 10

(Octal Bit 12)

Decimal Bit 09

(Octal Bit 11)

Data Format

0

0

BCD

0

1

not used

1

0

two's complement binary

1

1

signed magnitude binary

Input Type

Data Format