Default configuration – Rockwell Automation 1771-IFE , D17716.5.90 USER MNL. ANALOG INPUT Module User Manual

Page 37

Advertising
background image

Module Configuration

Chapter 4

4-8

If a write block of five words, with all zeroes, is sent to the Analog Input
Module (cat. no. 1771-IFE), default selections will be:

1 to 5V DC or 4 to 20mA (dependent on configuration jumper setting)
BCD data format
no real time sampling (RTS)
no

filtering

no

scaling

single-ended

inputs

Figure 4.3

Analog Input Module (1771ĆIFE) Block Transfer Write Configuration

Block

Decimal Bits 15 14 13 12

11

10 09

08

07 06 05 04 03 02 01 00

Description

Octal Bits

17 16 15 14

13

12 11

10

07 06 05 04 03 02 01 00

Description

Word 1

8

7

6

5

4

3

2

1

Range Selection Ć Channels 1 thru 8

2

16

15

14

13

12

11

10

9

Range Selection Ć Channels 9 thru 16

3

Real Time Sampling

Data

Format

Input

Type

Digital Filter

Real time sampling, data format, input

type and digital filter

4

16 15 14 13

12

11 10

9

8

7

6

5

4

3

2

1 Sign Bits, minimum scaling values

5

16 15 14 13

12

11 10

9

8

7

6

5

4

3

2

1 Sign Bits, maximum scaling values

6

Channel 1 Ć minimum scaling

7

Channel 1 Ć maximum scaling

8

Channel 2 Ć minimum scaling

9

Channel 2 Ć maximum scaling

10

Channel 3 Ć minimum scaling

37

Channel 16 Ć maximum scaling

Default Configuration