Default configuration – Rockwell Automation 1771-IFE , D17716.5.90 USER MNL. ANALOG INPUT Module User Manual
Page 37

Module Configuration
Chapter 4
4-8
If a write block of five words, with all zeroes, is sent to the Analog Input
Module (cat. no. 1771-IFE), default selections will be:
1 to 5V DC or 4 to 20mA (dependent on configuration jumper setting)
BCD data format
no real time sampling (RTS)
no
filtering
no
scaling
single-ended
inputs
Figure 4.3
Analog Input Module (1771ĆIFE) Block Transfer Write Configuration
Block
Decimal Bits 15 14 13 12
11
10 09
08
07 06 05 04 03 02 01 00
Description
Octal Bits
17 16 15 14
13
12 11
10
07 06 05 04 03 02 01 00
Description
Word 1
8
7
6
5
4
3
2
1
Range Selection Ć Channels 1 thru 8
2
16
15
14
13
12
11
10
9
Range Selection Ć Channels 9 thru 16
3
Real Time Sampling
Data
Format
Input
Type
Digital Filter
Real time sampling, data format, input
type and digital filter
4
16 15 14 13
12
11 10
9
8
7
6
5
4
3
2
1 Sign Bits, minimum scaling values
5
16 15 14 13
12
11 10
9
8
7
6
5
4
3
2
1 Sign Bits, maximum scaling values
6
Channel 1 Ć minimum scaling
7
Channel 1 Ć maximum scaling
8
Channel 2 Ć minimum scaling
9
Channel 2 Ć maximum scaling
10
Channel 3 Ć minimum scaling
⇓
⇓
⇓
⇓
37
Channel 16 Ć maximum scaling
Default Configuration