Module Configuration

Chapter 4

4-7

Important: Scaling values must always be entered in BCD format,
even if the data format chosen is binary. If scaling is selected for any
channel, all channels must be scaled. If scaling is not required on certain
channels, set those to the default input range: 0 to 4095 for 0 to + voltage
or current ranges, and -4095 to +4095 for - to + voltage or current ranges.

If scaling is not selected, the module requires specific minimum BTR
file lengths for the number of channels used.
The BTW file length can
be set to 3 words. Table 4.F shows the required BTW and BTR file lengths.

Table 4.F

Block Transfer Read and Write File Lengths

Channels

Used

BTR File

Length

BTW File

Length

1

5

7

2

6

9

3

7

11

4

8

13

5

9

15

6

10

17

7

11

19

8

12

21

9

13

23

10

14

25

11

15

27

12

16

29

13

17

31

14

18

33

15

19

35

16

20

37

Important: Use decimally addressed bit locations for PLC-5 processors.