5 - module status and input data, Module status and input data, Chapter objectives reading data from your module – Rockwell Automation 1771-IFE , D17716.5.90 USER MNL. ANALOG INPUT Module User Manual

Page 39

Advertising
background image

Chapter

5

5-1

Module Status and Input Data

In this chapter you will read about:

reading data from your module
block transfer read block format

Block transfer read programming moves status and data from the input
module to the processor’s data table in one I/O scan (Figure 5.1). The
processor’s user program initiates the request to transfer data from the
input module to the processor.

Figure 5.1

Word Assignments for Analog Input Module (1771ĆIFE)

Block Transfer Read

Decimal Bits 15 14 13 12 11 10 09 08 07 06 05 04 03 02

01

00

Description

Octal Bits

17 16 15 14 13 12 11 10 07 06 05 04 03 02

01

00

Description

Word 1

Not Used

Diagnostic Bits

Diagnostics

2

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Data underrange for channels 1-16

1

3

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Data overrange for channels 1-16

1

4

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Data polarity for channels 1-16

5

Channel 1 Input

Channel 1 Input

6

Channel 2 Input

Channel 2 Input

7

Channel 3 Input

Channel 3 Input

8

Channel 4 Input

Channel 4 Input

20

Channel 16 Input

Channel 16 Input

1

These bits are set (1) at approximately the input range limits selected (Table 5.B).

Chapter Objectives

Reading Data From Your

Module

Advertising