Plcć5 programming – Rockwell Automation 1771-IFE , D17716.5.90 USER MNL. ANALOG INPUT Module User Manual

Page 28

Advertising
background image

Module Programming

Chapter 3

3-4

The PLC-5 program is very similar to the PLC-3 program with the
following exceptions:

1.

You must use enable bits instead of done bits as the conditions on
each rung.

2.

A separate control file must be selected for each of the block transfer
instructions. Refer to Appendix B.

Figure 3.3

PLCĆ5 Family Sample Program Structure

BTR Enable

EN

DN

Pushbutton

Power-up Bit

BTW Enable

1

2

Bit

ER

EN

DN

ER

BTR

BLOCK TRANSFER READ

RACK:

GROUP:

MODULE:

CONTROL:

DATA FILE:

LENGTH:

CONTINUOUS:

N

BTW

BLOCK TRANSFER WRITE

RACK:

GROUP:

MODULE:

CONTROL:

DATA FILE:

LENGTH:

CONTINUOUS:

N

XX:XX

X

X

X

X

XX:XX

XX:XX

X

X

X

X

XX:XX

10956ĆI

Program Action

Rungs 1 and 2

At powerĆup, the program enables a block

transfer read and examines the powerĆup bit

in the BTR file (rung 1). Then, it initiates one

block transfer write to configure the module

(rung 2). Thereafter, the program continuously

reads data from the module (rung 1).

A subsequent BTW operation is enabled by a

pushbutton switch (rung 2). Changing

processor mode will not initiate a block

transfer write.

PLCĆ5 Programming