Programming Examples

Appendix B

B-4

The following is a sample procedure for entering data in the configuration
words of the block transfer write instruction when using a PLC-5 processor
and 6200 programming software.

1.

Enter the following rung:

EN

DN

BLOCK XFER WRITE

RACK :

GROUP :

MODULE:

CONTROL:

ER

DATA FILE:

LENGTH:

CONTINUOUS:

X

X

X

XX:XX

N7:60

37

N

BTW ENABLE

N7:60 is the address of the BTW transfer file

2.

Press [F8] (data monitor),[F5] (change address) and enter N7:60 to
display the configuration block.

The industrial terminal screen should look like Figure B.3.

Figure B.3

Sample PLCĆ5 Data File (Hexadecimal Data)

ADDRESS

N7:70

N7:60

N7:90

N7:80

0085

5003

0000

0000

0040

00FF

0000

0000

0085

00FF

0000

0000

0040

0040

0000

0000

0085

0085

0000

0000

0040

0040

0000

0000

0085

0085

0000

0000

0040

0040

0000

0085

0085

0000

0000

0040

0000

0

1

2

3

4

5

6

7

8

9

3.

Enter the data corresponding to your bit selections and add scaling
values, if scaling is desired.

4.

[ESC] returns you to the ladder program.

PLCĆ5 Family Processors