Programming Examples
Appendix B
B-4
The following is a sample procedure for entering data in the configuration
words of the block transfer write instruction when using a PLC-5 processor
and 6200 programming software.
1.
Enter the following rung:
EN
DN
BLOCK XFER WRITE
RACK :
GROUP :
MODULE:
CONTROL:
ER
DATA FILE:
LENGTH:
CONTINUOUS:
X
X
X
XX:XX
N7:60
37
N
BTW ENABLE
N7:60 is the address of the BTW transfer file
2.
Press [F8] (data monitor),[F5] (change address) and enter N7:60 to
display the configuration block.
The industrial terminal screen should look like Figure B.3.
Figure B.3
Sample PLCĆ5 Data File (Hexadecimal Data)
ADDRESS
N7:70
N7:60
N7:90
N7:80
0085
5003
0000
0000
0040
00FF
0000
0000
0085
00FF
0000
0000
0040
0040
0000
0000
0085
0085
0000
0000
0040
0040
0000
0000
0085
0085
0000
0000
0040
0040
0000
0085
0085
0000
0000
0040
0000
0
1
2
3
4
5
6
7
8
9
3.
Enter the data corresponding to your bit selections and add scaling
values, if scaling is desired.
4.
[ESC] returns you to the ladder program.