Installing Your ControlNet Adapter Module

2–5

Publication 1771-6.5.123 – May 1996

You must set the I/O chassis backplane switches and power-supply
configuration plug.

Backplane Switch Assembly

This switch assembly is located on the backplane of the I/O chassis.
You use it to select:

the last state of all outputs

the processor restart lockout feature

1/2-, 1- or 2-slot addressing

Figure 2.3
I/O Chassis Backplane Switch Assembly Settings for ControlNet
Adapter Module in PLC-5/20C and PLC-5/40C Processor Systems

Processor Restart Lockout (PRL) –

ON Processor can restart the I/O chassis

after a communication fault. Set this
switch to ON if you plan to use I/O rack
auto-configuration.

OFF The I/O chassis must be restarted at

the chassis.

Last State Switch -

ON Outputs of this chassis remain in last state when a

communication fault is detected by the adapter.

OFF Outputs of this I/O chassis are deenergized when a

communication fault is detected by this adapter

Always OFF

10802-I

O

O

1

2

345

6

7

8

N

F

F

OFF

ON

You select 1/2-slot addressing

ON

OFF

You select 1-slot addressing

OFF

OFF

You select 2-slot addressing

ON

ON

Not allowed

Addressing Switches
5 6

Always OFF

ATTENTION: If switch 1 is set to the ON position, outputs
connected to this chassis remain in their last state when
a fault occurs and machine motion may continue after
fault detection. We recommend that you set switch 1 to
the OFF position to deenergize outputs wired to this
chassis when a fault is detected.