Look carefully at the status display and OK indicator when powering
up the module. These indicators provide meaningful information on
proper module operation.

1. Apply power to the chassis – the OK indicator should not light.

2. The module runs a power on self test (POST). During this test,

the status displays 0000 through 8888.

3. If the OK indicator is red, and the display shows POST-RSET,

then POST has failed.

a. Press the reset pushbutton to reset.

The module reruns the POST program. If POST-RPLC
appears on the status display again, POST has failed again.

b. Replace the module.

4. If:

a. the OK indicator begins to blink green, and

b. the series/revision level of the module is displayed in the

status window (e.g. A/A, A/B, etc.), and

c. the channel A and B indicators blink alternately, the module

has passed POST.

If the indications are neither of those indicated in 3 or 4, refer to
chapter 5, “Troubleshooting.”

5. The module status displays INIT-A#nn (where nn is the node

number of module).

6. The channel indicators indicate network condition as shown in

the indicator table in chapter 5.

7. Then the display shows IDLE-A#nn (where nn is the node

number of module), indicating a successful configuration by the
ControlNet Configuration Manager.

For detailed information on planning and installing your ControlNet
system, see the following publications:

Publication

Publication Number

ControlNet Cable System Component List

AG-2.2

ControlNet Cable System Planning and Installation Manual

1786-6.2.1

ControlNet Coax Tap Installation Instructions

1786-2.3

ControlNet Network Access Cable Installation Instructions

1786-2.6

ControlNet Repeater Installation Instructions

1786-2.7

Industrial Automation Wiring and Grounding Guidelines

1770-4.1

In this chapter you learned how to install your adapter module.
Chapter 3 tells you how to address your I/O.

OK

STATUS

NET

ADDRESS

Status

OK Indicator

Reset pushbutton

Channel A and B
indicators

INIT
A#nn

IDLE
A#nn

More

Powerup Sequence

Chapter Summary