Ok indicator and display mnemonics – Rockwell Automation 1771ACN/B_1771ACNR/B,D17716.5.123 U.MNL CONTROLNET ADAPTER User Manual

Page 44

Advertising
background image

Troubleshooting

5–2

Publication 1771-6.5.123 – May 1996

OK Indicator and Display Mnemonics

OK Indicator

Display

Mnemonic

NET

SS

Descr

n

Pr

a le ause

Rec

en e Ac

n

OK

Red/
Green

STATUS

T

ADDRESS

Description

Probable Cause

Recommended Action

Off

Off

None

Module not communicating

Power supply fault

Check power supply, cable
connectors, and seat adapter firmly
in chassis.

Defective adapter

Contact Allen-Bradley service.

POST

Adapter is running Power On Self Test

None

None

CODE
UPDT

Firmware update mode.

Adapter firmware is being
updated via A-B Flash Update
Utility.

None

Blinking Red

POST
RSET

Module failed Power On Self Test

RAM or FLASH test failed.
Processor fault or watchdog
timeout.

Push the reset pushbutton on the
front of the module.

A#00
ERR

Illegal ControlNet address.

Network address set to 00.

Power down the adapter and change
the network address switches.

MOD
ERR

I/O module placement error.

Incorrect I/O module density for
addressing mode used.

Place I/O module in correct slot in
chassis.

RACK
ERR

Illegal backplane switch settings.

Illegal addressing mode selected.

Power down the adapter and change
the backplane switches.

PRL

Adapter in processor restart lockout
mode. (Adapter to processor link is
normal.)

Processor restart lockout switch
on chassis backplane in on
position.

Depress reset button on module to
clear lockout feature, or cycle power.

SHRT
BP

Communication on link. Excessive
noise on backplane or possible shorted
backplane

I/O module or chassis backplane
bad.

Replace module or chassis as
necessary.

DUPL
NODE

Duplicate node.

Another adapter with the same
ControlNet address is on the link.

Power down the adapter and change
the network address switches to
correct node.

SW
ERR

Switch error.

Network address switches have
been changed since module
powerup.

Set network address switches to
correct address and cycle power to
the adapter.

Red

RPLC

Fatal Power On Self Test failure.

RAM or FLASH test failed.
Processor fault or watchdog
timeout.

Contact Allen-Bradley service.

None

Hardware fault.

Defective hardware.

Blinking Green

INIT

Requires ControlNet configuration.

No communication with
ControlNet Configuration
Manager node.

Verify Configuration Manager node is
operating.

IDLE

Processor not actively controlling I/O.

Adapter not mapped.

Verify mapping of adapter in
processor.

NET
ERR

Nework error.

Cable error or no other nodes on
network.

Verify network cabling.