Wiring the home limit switch input, Figure 4 wiring the ok contacts, Figure 5 – Rockwell Automation 1756-HYD02 ControlLogix Hydraulic Servo Module User Manual

Page 11

Advertising
background image

ControlLogix™ Hydraulic Servo Module 11

Publication

1756-IN580A-EN-P - March 2003

Wiring the Home Limit Switch Input

The home limit switch inputs to the servo module are designed for
24V dc nominal operation. These inputs should be wired for current
sourcing operation.

Figure 4

Wiring the OK Contacts

A set of isolated solid- state OK relay contacts is provided for optional
interface to an E- stop string, which controls power to the associated
pumps. The OK contacts are rated to drive an external 24V dc pilot
relay (for example, Allen-Bradley 700- HA32Z24) whose contacts can
be incorporated into the E- Stop string as in Figure 5.

Figure 5

From
1756-HYD02

HOME

IN_COM

24 V dc

Power

Supply

+

43396

General cable
C0720

From
1756-HYD02

+OK

-OK

24 V dc

Power

Supply

+

43397

OK Pilot
Relay

43398

OK Pilot
Relay
Contacts

Start

Stop

CR1

CR1

CR1

M1

24V ac/dc or
120V ac
typical

General cable
C0720