Rockwell Automation 1756-HYD02 ControlLogix Hydraulic Servo Module User Manual

Page 14

Advertising
background image

14 ControlLogix™ Hydraulic Servo Module

Publication

1756-IN580A-EN-P - March 2003

Understanding Module Status Using the FDBK Indicator

Flashing red
light

One of the following:

· A major recoverable

failure has occurred.

· A communication fault,

timer fault, or
non-volatile memory
storage (NVS) update is
in progress.

· The OK contact has

opened.

If an NVS update is in progress,
complete the NVS update.
If an NVS update is not in progress:

· Check the Servo Fault word for the

source of the error.

· Clear the servo fault condition via

Motion Axis Fault Reset instruction.

· Resume normal operation.

· If the flashing persists, reconfigure

the module.

Steady red light

One of the following:

· A potential non-

recoverable fault has
occurred.

· The OK contact has

opened.

· Reboot the module.

· If the solid red persists, replace the

module.

IMPORTANT

Make sure that any transducer used with the
1756-HYD02 module uses an external
interrogation signal.

If the OK
indicator
displays:

The module status is:

Take this action:

AX0 AX1

FDBK

DRIVE

OK

HYDRAULIC

FDBK

DRIVE

Feedback