ControlLogix™ Hydraulic Servo Module 17

Publication

1756-IN580A-EN-P - March 2003

Flashing red
light

The axis drive output is in
the shutdown state.

· Check for faults that may have

generated this state.

· Execute the Shutdown Reset motion

instruction.

· Resume normal operation.

Steady red light

The axis drive is faulted.

· Check the drive status.

· Clear the Drive Fault condition at the

drive.

· Clear the servo fault condition using

the Motion Axis Fault Reset
instruction.

· Resume normal operation.

· Check the configuration for the Drive

Fault.

· If configured to be

normally open and there is
no voltage, this is the
normal condition.

· If configured to be

normally closed and 24V dc
is applied, this is the
normal condition.

If the DRIVE
indicator
displays:

The module status is:

Take this action: