Rockwell Automation 1756-HYD02 ControlLogix Hydraulic Servo Module User Manual

Page 22

Advertising
background image

22 ControlLogix™ Hydraulic Servo Module

Publication

1756-IN580A-EN-P - March 2003

ESD Immunity

IEC 61000-4-2:
6kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 80MHz to
2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on signal ports

Surge Transient
Immunity

IEC 61000-4-5:
+2kV line-earth (CM) on shielded ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz

Enclosure Type Rating

None (open-style)

Certifications

(when product is marked)

UL

UL Listed Industrial Control Equipment

CSA CSA Certified Process Control Equipment
CSA CSA Certified Process Control Equipment for

Class I, Division 2 Group A,B,C,D Hazardous
Locations

CE

(4)

European Union 89/336/EEC EMC Directive,
compliant with:

EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions

C-Tick

(4)

Australian Radiocommunications Act,
compliant with:

AS/NZS 2064; Industrial Emissions

(1)

Maximum wire size requires the extended-depth RTB housing (1756-TBE).

(2)

Use the conductor category information for planning conductor routing as described in the system
level installation manual.

(3)

Refer to Industrial Automation Wiring and Grounding Guidelines, publication number 1770-4.1.

(4)

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and
other certification details.