Checking the led indicators, Understanding module status using the ok indicator – Rockwell Automation 1756-HYD02 ControlLogix Hydraulic Servo Module User Manual

Page 13

Advertising
background image

ControlLogix™ Hydraulic Servo Module 13

Publication

1756-IN580A-EN-P - March 2003

Checking the LED Indicators

The module uses a single bi-colored LED to indicate module OK
status and bi-colored LED indicators to show individual feedback
(FDBK) and drive (DRIVE) status for both axes.

During power up, the module completes an indicator test. The OK
indicator turns red for 1 second and then turns to flashing green if the
module passes all its self tests.

Understanding Module Status Using the OK Indicator

The table below offers an explanation of the OK indicator.

If the OK
indicator
displays:

The module status is:

Take this action:

Off

The module is not operating.

· Apply chassis power.

· Verify the module is completely

inserted in chassis and backplane.

Flashing green
light

The module has passed
internal diagnostics, but it is
not communicating axis
data over the backplane.

· None, if you have not configured the

module.

· If you have configured the module,

check the slot number in the
1756-HYD02 Properties dialog box.

Steady green
light

One of the following:

· Module is exchanging

axis data.

· The module is in the

normal operating state.

None

AX0 AX1

FDBK

DRIVE

OK

HYDRAULIC

FDBK

DRIVE

OK indicator

Advertising