FLEX I/O Isolated Output HART Analog Module 17

Publication

1794-IN120C-EN-P - April 2009

Channel Analog Fault Mode Selection

Analog Fault Mode

Decimal Value

Bits

9

8

1

0

Min Scale

0

0

0

Max Scale

1

0

0

Hold Last State

2

1

0

User Specifed Data Value

3

1

1

HART Current Ratio

HART Current
Ratio Limit

Decimal Value

Bits

15

14

13

12

11

7

6

5

4

3

Disabled

0

0

0

0

0

0

Not applicable

1

0

0

0

0

1

Not applicable

2

0

0

0

1

0

Not applicable

3

0

0

0

1

1

Not applicable

4

0

0

1

0

0

5%

5

0

0

1

0

1

6%

6

0

0

1

1

0

7%

7

0

0

1

1

1

8%

8

0

1

0

0

0

9%

9

0

1

0

0

1

10%

10

0

1

0

1

0

30%

30

1

1

1

1

0

31%

31

1

1

1

1

1

Advertising