8 FLEX I/O Isolated Output HART Analog Module

Publication

1794-IN120C-EN-P - April 2009

3. Make sure the pins on the bottom of the module are straight

so they align properly with the connector in the terminal base.

4. Position the module (4) with its alignment bar (5) aligned with

the groove (6) on the terminal base.

5. Press firmly and evenly to seat the module in the terminal base

unit, noting that the module is seated when the latching
mechanism (7) is locked into the module.

Wire the Module

To connect wiring for 1794-TB3 and 1794-TB3S bases, refer to the
tables and figure and complete the following.

1. Connect individual output wiring to numbered terminals on

the 0…15 row A, as indicated in the table, using Belden 8761

cable for signal wiring.

WARNING

If you remove or insert the module while the backplane power is on, an
electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
before proceeding.

WARNING

If you connect or disconnect wiring while the field-side power is on, an
electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
before proceeding.

ATTENTION

Connect only one current signal per channel.