Rockwell Automation 1794-OF8IH FLEX I/0 8 Isolated Output Analog Module User Manual

Page 9

Advertising
background image

FLEX I/O Isolated Output HART Analog Module 9

Publication

1794-IN120C-EN-P - April 2009

2. Connect each channel signal return to the associated terminal

on row A.

3. Connect the +V DC power lead to terminal 34 on the 34…51

row C, and the -V common/return to terminal 16 on the

16…33 row B.

4. If daisy-chaining power to the next terminal base, connect a

jumper from terminal 51 (+V DC) on this base unit to
terminal 34 on the next base unit.

5. If continuing DC common to the next base unit, connect a

jumper from terminal 33 (common) on this base unit to
terminal 16 on the next base unit,

6. For both 1794-TB3 and 1794-TB3S bases, connect wiring

shields to functional earth ground as near as possible to the
module.

ATTENTION

To reduce susceptibility to noise, power analog modules and digital modules
from separate power supplies.

Do not exceed a length of 3 m (9.8 ft) for DC power cabling.

Advertising