18 FLEX I/O Isolated Output HART Analog Module
Publication
1794-IN120C-EN-P - April 2009
Channel Data Formats
Format
(1)
Bits
Format
Name
Signal Range User Range
Resolution
15 14 13 12
11 10 9
8
7
6
5
4
LO
HI
LO
HI
3
2
1
0
0
0 0 0 0 0…20 mA in
Milliamps
0.00
22.00
0
(0.000 mA)
22000
(22.000 mA)
1.0 µA
1
0 0 0 1 0…20 mA in
% Full Scale
0.00
22.00
0
(0%)
11000
(110.00%)
2.0 µA
3
0 0 1 1 0…20 mA in
UINT
0.00
20.00
0
65535
0.3052 µA
4
(2)
0 1 0 0 4…20 mA in
Milliamps
2.00
22.00
2000
(2.000 mA)
22000
(22.000 mA)
1.0 µA
7
(2)
0 1 1 1 4…20 mA in
UINT
4.00
20.00
0
65535
0.2441 µA
14
(2)
1 1 1 0 4…20 mA in
% Full Scale
2.00
22.00
-1250
(-12.50%)
11250
(112.50%)
1.6 µA
(1)
All other formats are invalid.
(2)
HART Communications supported with these data formats only.