FLEX I/O Isolated Output HART Analog Module 23

Publication

1794-IN120C-EN-P - April 2009

Status Indicator

The OK status indicator is bicolor, red, and green. The indicator
flashes green for these reasons:

The module configuration word is zero (for example,
powerup reset condition).

The 24V DC user power is off.

The module is in Configuration mode.

The indicator displays red to indicate the module did not pass the
initial hardware test. Recycle power in response to this display.

After powerup, if the status indicator is not flashing green or solid
green, recycle module power to verify a proper reset of the bus
interface.

Specifications

FLEX I/O Isolated Output Analog Module - 1794-OF8IH

Attribute

Value

Number of outputs

8 isolated

Module base

Catalog numbers 1794-TB3, 1794-TB3S

Resolution

16 bits - unipolar

Current

0.305 µA/cnt unipolar

Data format

Engineering Units

(3)

Percent of Full Scale

RAW/Proportional Count

Update rate

10 ms

Output current terminal

4…20 mA (user configurable)

0…20 mA (user configurable)

Settling Time

70 ms, 0…99.9%

Load resistance

0

Ω

… 750

Ω

standard

Load reactance, max

10 µH