Rockwell Automation 1794-OF8IH FLEX I/0 8 Isolated Output Analog Module User Manual
Page 26
Advertising
26 FLEX I/O Isolated Output HART Analog Module
Publication
1794-IN120C-EN-P - April 2009
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
Emissions
CISPR 11:
Group 1, Class A
ESD Immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B Immunity
IEC 61000-4-4:
±3 kV at 5 kHz on signal ports
Surge Transient
Immunity
IEC 61000-4-5:
±2 kV line-earth(CM) on shielded ports
Conducted RF Immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
Environmental
Attribute
Value
Advertising