10 about program properties, 11 about program execution – Rockwell Automation AutoMax Enhanced Ladder Editor User Manual

Page 15

Advertising
background image

1Ć7

1.10

About Program Properties

The Program Properties dialog box contains three tabs:

Use this tab: For:
Program Info

viewing information about the program

Scan Info

defining how the program should be

scanned and the program's scan time.

Error Log

viewing the online error log

To access Program Properties from the File menu
Step 1.

Make sure no rung or instruction is selected.

Step 2.

From the File menu, choose Properties. The Program

Properties dialog box is displayed.

To access Program Properties from the popĆup menu
Step 1.

Make sure no rung or instruction is selected, and position

the mouse in the program's grid area away from any

instruction or wire.

Step 2.

Press the right mouse button. A popĆup menu is

displayed.

Step 3.

From the popĆup menu, choose Properties. The Program

Properties dialog box is displayed.

See the AutoMax Enhanced Ladder Language Reference manual,

J2Ć3094, for how to interpret the entries in the error log. See section

1.11 below for defining program scan time.

1.11

About Program Execution

Programs can execute by being scanned or eventĆdriven. An event

is a flag or indicator that one program can set or raise and another

program can wait for.
Scanned programs execute based on the scan time in ticks you

define. For a ladder program, you can define how often you want

the program to execute by defining scan time in ticks. The actual

scan time of a program is determined by this formula:
scan time (ms) = tick rate of the Processor module * number of

ticks.
You define the tick rate for the Processor module when you add it to

your rack configuration. By changing the tick rate, you can change

the time base for program execution. This allows you to run a

program based on a unit of your choice. You can set the tick rate in

increments of 0.5 ms between 0.5 ms and 10.0 ms. The default

value is 5.5 ms. The tick rate is defined separately for each

Processor in a rack. For more information, see section 1.11.1.
EventĆdriven programs can be controlled by either hardware events

or software events. When an eventĆdriven is first started (run), the

program executes once to completion. After this initial execution, the

program then waits for the designated event to occur. If you have

program logic that you do not want to run during the initial execution

of the program, use the preĆdefined first_scan variable. An example

is shown here: