5 connecting instructions (drawing wires) – Rockwell Automation AutoMax Enhanced Ladder Editor User Manual

Page 24

Advertising
background image

2Ć6

2.5

Connecting Instructions (Drawing Wires)

Connect instructions when you want to create branches (parallel

logic) or to connect two or more instructions together that were

placed too far apart for them to connect automatically. Connect

instructions by drawing wires.
You can use the grid markers to help you determine where

instructions will be placed and where you can draw wires.

To connect instructions
Step 1.

Place the cursor near a connection point for an

instruction. For relay logic, the connection point is either

the left side (for coils) or both sides (for contacts). For

block instructions, the connection points are the free

ends of the long lines.
When the cursor is near a connection point, it changes to
include a pencil:

Step 2.

Press and hold the left mouse button. The cursor

changes to a pencil.

Step 3.

Draw the wire by moving the mouse towards the

instruction to which you want to connect. You can draw a

continuous wire to connect instructions in a branch and

the coils at the end of the rung. A dotted line indicates

where the wire will be placed.

Step 4.

When you reach the destination connection point, release

the mouse button.
The wire is drawn to connect the instructions.

2.6

Connecting Multiple Instructions by Using

the ENO Output Bit

Quickly build a rung by connecting a relay instruction or a Boolean

input of an instruction to the ENO output parameter of an instruction

block. For example:

The Boolean input parameter's or relay instruction's state is linked to

that of the ENO output parameter.
The ENO output parameter for an instruction follows the state of

that instruction's EN input parameter unless an error occurs.

When an error occurs within an instruction, the ENO output

parameter is set according to the preĆdefined variable

ERROR_ENO. Because the default value of ERROR_ENO is

false, instructions connected to the ENO output are disabled

when an error occurs in the instruction block containing the ENO

output. Should you want to continue evaluating and executing the

logic connected to an ENO output, set the variable ERROR_ENO

true.