Rockwell Automation AutoMax Enhanced Ladder Editor User Manual

Page 59

Advertising
background image

5Ć13

5.11

Capturing the State of Logic in an Online

Program

While monitoring a program, you can freeze or capture the power

flow of a given rung using the Capture Trigger command from the

Online menu. When the trigger is activated (becomes true), the state

of the rung is captured and displayed. The rung's power flow

information is not updated on the computer; however, it continues to

run on the Processor. The Editor obtains trigger information from the

Processor. You can capture a rung's status based on one of the

following conditions:
D a coil turns on
D a coil turns off
D an error occurs with an instruction in a rung
If more than one coil exists, the coil used for the trigger is a rung's

upperĆrightĆmost coil. Once a trigger is set, it is active on the next

program scan. Triggers are edgeĆsensitive. (For example, a coilĆon

trigger is activated the next time that the coil goes true.)
Only one trigger can be set for a rung, but you can set multiple

triggers in an online program. The only limitation is the amount of

available Processor memory.
Triggers are local to the computer that set the trigger. Other online

connections cannot view these triggers until they are activated.
A trigger remains set as long as the rung is displayed in the online

program window. Once the triggered rung scrolls off the screen, the

trigger is cleared. Also, closing an online program window clears all

the triggers set in the program.
Rungs that have triggers set are indicated by a letter displayed in

the rung status area representing the trigger type, either an o", f",

or e". When a trigger is activated, this indicator is replaced by a T."

If a rung is marked by a revision mark, the trigger indicator replaces

the revision mark until the trigger is cleared.
This table summarizes some points to keep in mind if you set

triggers on rungs that already contain a trigger.

If a rung already has a trigger set

and you:

Then the Editor:

D modify the rung, or
D scroll the rung off the screen, or
D close the program window

clears the trigger

select the same trigger type for a new

trigger

resets the trigger

select a different trigger type for a

new trigger

clears the current

trigger and assigns

the new trigger to the

rung

The Editor notifies you when another online connection has set a

trigger for the same rung.