2 initial installation – Rockwell Automation 61C345 4 Input 4-20mA Analog Rail Module User Manual

Page 16

Advertising
background image

3Ć2

3.2

Initial Installation

Use the following procedure to install the Analog Rail module.
Step 1.

Using the mounting dimensions shown in figure 3.1,

prepare the necessary mounting provisions on the panel.

The module is designed to be mounted vertically using

four #10 or M5 bolts or studs. Multiple modules should

be mounted side by side. The flange width of two

modules side by side is sufficient to dissipate the heat

produced by the modules. The modules can also be

mounted one above the other, but since this hardware

configuration does not allow the most efficient heat

dissipation, the minimum clearance between the module

chassis is 3". See figure 3.1.

7.0"

9.25"

Depth: 7.75"

Diameter of mounting holes: 7/32"

2.44"

3.0"

2.94"

Figure 3.1 Ć Mounting Dimensions