Step 12. Attach the original 12Ćpoint and 4Ćpoint connectors with

wiring to the faceplate of the module. Use the stud

marked GND" (ground) on the bottom right flange of the

module to connect a ground wire.

Step 13. Set the Mode" switch on the faceplate to the desired

position.

Step 14. Connect the I/O Rail cable between the Analog Rail

connection labeled Input" and any rail connector on the

Reliance device that will communicate with the module.

Turn on power to the Reliance device connected to the

Analog Rail module. Recall that the Mode switch is read

each time the Reliance device connected to the module is

powered up. If applicable, reĆconnect the cable between

the Local I/O Head, or the DCS 5000/AutoMax Remote

I/O Head, and the host.

Step 15. Turn on power to the Analog Rail module Input Power"

connections.

Step 16. Turn on power to the external hardware connected to the

Analog Rail module.

Step 17. Verify that the hardware has been installed correctly.

For AutoMate systems, use the APX Point Monitor

function to test the module. To test the input channels,

verify that the input signal in the channel (4Ć20mA) is

proportional to an ammeter reading at the terminal points.
For DCS 5000, AutoMax, or Distributed Power DĆC Drive

systems, use the DCS 5000 or AutoMax Programming

Executive software I/O Monitor function, respectively. To

test the input channels, verify that the input signal in the

channel (4Ć20mA) is proportional to an ammeter reading

at the terminal points.