3Ć4

Channel

Terminal

Number

Terminal

Label

Signal

0

1

2

3

IĆIN

Common

(no label)

4Ć20mA+ input

common

(shield; no connection)*

1

4

5

6

IĆIN

Common

(no label)

4Ć20mA+ input

common

(shield; no connection)*

2

7

8

9

IĆIN

Common

(no label)

4Ć20mA+ input

common

(shield; no connection)*

3

10

11

12

IĆIN

Common

(no label)

4Ć20mA+ input

common

(shield; no connection)*

*This terminal makes no electrical connection to the Analog Rail printed circuit

board.

Step 10. For each ofthe four input channels, connect a shield wire

from the external hardware to the third terminal (terminals

3, 6, 9 and 12, respectively) on each channel. The shield

wire at the external hardware end ofthe cable should be

connected to the source reference point. See figure 3.2.