Step 5.

Replace the 32mA fuse(s) that has blown following the

directions below.
a) Stop any application tasks that are running.
b) Turn off power to the external hardware connected to

the module. Turn off power (120 VAC or 24 VDC) to

the module.

c) Without disconnecting the wiring, remove the 12Ćpoint

connector from the faceplate and set aside. Without

disconnecting the wiring, remove the 4Ćpoint

connector from the faceplate and set aside.

d) Before disassembling the module, note that it consists

of two major pieces, the metal enclosure and the

printed circuit board, which is screwed to the left side

of the enclosure (if facing the front of the module).

After the screws are removed, the two pieces can be

seperated in a manner similar to that of opening a

book. Simply pull the left side of the module

(including the faceplate) to the left away from the

remainder of the metal enclosure. See below for the

screws that need to be removed. If some of the

screws are inaccessible, remove the entire module

from the cabinet before proceeding.

Module

Faceplate

3 screws

on top

3 screws on bottom

3 screws

on the right

2

screws

on left

Figure 5.1 Ć Disassembling the Module to Replace the 32mA Fuse