4 constant under-range, 4 constant underćrange – Rockwell Automation 61C345 4 Input 4-20mA Analog Rail Module User Manual

Page 36

Advertising
background image

5Ć4

Step 1.

Verify that the application program(s) is correct. Check to

see that the program is referencing the correct registers

(AutoMate) or symbolic names (DCS 5000/AutoMax). In

DCS 5000/AutoMax applications, make certain that the

program is not attempting to write to the input channels.

Step 2.

Stop any application tasks that are running. Turn off

power to the Analog Rail module.

Step 3.

Try to clear the condition by disconnecting and then

reconnecting the I/O Rail cable. Make certain the

connections are tight. If applicable, check the

connections between the host and the Local I/O Head,

the AutoMate Remote I/O Head, or the DCS 5000/AutoMax

Remote I/O Head. Check that the pins on the input

connector are not bent.

Step 4.

Turn off power to the external hardware. Verify that the

wiring to the external hardware is tight and functioning

correctly.

Step 5.

Turn on power to the external hardware.
For input channels, use the Executive software to read

the value on the input channels. Use an ammeter to read

the input signal and compare the two. If the signal is

being converted correctly, there is aproblem with the

external hardware or wiring.

Step 6.

Troubleshoot the external hardware, the wiring, and the

host.

5.4

Constant UnderĆRange

Problem: the underĆrange bit (12 decimal) on an input channel

register is constantly set to 1. Assuming that the power supply for

the external hardware connected to the input channel is providing

an input signal within the specified limits (4Ć20mA), the possible

causes of this problem are a loose connector on the analog input

section of the faceplate, loose or malfunctioning wiring, incorrect

(reversed) input signal wiring on the module faceplate, or a blown

input channel fuse (32mA fuse). Follow the steps below to isolate

the problem.
Step 1.

Stop any application tasks that are running. Turn off

power to the external hardware connected to the module.

Turn off input power (120 VAC or 24 VDC) to the module.

Step 2.

Verify that the 12Ćpoint connector on the analog section of

the module faceplate is securely attached to its mating

half.

Step 3.

Verify that the signal wiring on the module faceplate is

correct. See step 9 in section 3.2 for more information.

Verify that the wiring is tight and functioning properly.

Step 4.

Turn on power to the module and to the external

hardware. Use the Executive software to read the value

on the input channel. Use an ammeter to read the input

signals at the terminal point and compare the two. If both

read zero, verify that the external hardware is operating

correctly. If the external hardware is operating correctly,

the 32mA fuse for the input channel may be blown.