Rockwell Automation 1799-D16U16BAGL 16 Input/16 Output Digital and 2 Input/2Output Analog  User Manual

Page 13

Advertising
background image

16 Input/16 Output Digital and 2 Input/2 Output Analog Embedded I/O Boards 13

Publication 1799-IN011A-EN-P - February 2007

Connect the Field Input Device to the I/O Connector (P5)

The inputs on these boards are isolated in two groups of eight, with each group providing a
separate common signal. Inputs 0…7 share the common in GRP 0 signal. Inputs 8…15 share
the common in GRP 1 signal.

The 1799-D16U16BAGL and 1799-D16U16VAGL boards have universal inputs that allow
operation with either sourcing or sinking input devices. The universal feature lets you
configure the inputs as either sinking or sourcing. Use the following wiring diagrams to
connect each group of inputs on the boards.

Inputs (Sinking)

Inputs (Sourcing)

IMPORTANT

All field input devices in each group of eight must be of the same type,
either sinking or sourcing. The board will not operate if the types are
mixed.

Pins 6, 7, 21,

23, 37-40

Input X

Pins 25-28,
41, 42, 44, 45
Input X

Pin 43

Common In

GRP 1

GRP 0

GRP 1

+

_

+

_

42565

Pin 22

Common In

GRP 0

Pins 6, 7, 21,
23, 37-40

Input X

Pin 22

Common In

GRP 0

42566

Pins 25-28,

41, 42, 44, 45

Input X

Pin 43
Common In

GRP 1

GRP 0

GRP 1

+

_

+

_

Advertising
This manual is related to the following products: