Rockwell Automation 1799-D16U16BAGL 16 Input/16 Output Digital and 2 Input/2Output Analog  User Manual

Page 30

Advertising
background image

30 16 Input/16 Output Digital and 2 Input/2 Output Analog Embedded I/O Boards

Publication 1799-IN011A-EN-P - February 2007

Environmental Specifications

Enclosure type rating

None (open-style)

Pilot Duty Rating

Pilot duty DC-14

LED indicators

Board Status indicator - red/green

Network Status indicator - red/green

DeviceLogix Status indicator - green

Input Point indicator - yellow

Output Point indicator - yellow

Dimensions (H x W x D), approx.

millimeters

(inches)


19.05 x 77.85 x 189.33 mm

(0.75 x 3.07 x 7.45 in.)

Weight

0.10 kg (0.22 lb)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, Publication 1770-4.1.

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IIEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20...70

°C (-4...158 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

-40...85 °C (-40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5...95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV indirect contact discharges

Radiated RF immunity

IEC 61000-4-3:

10 V/m with 1 kHz sine-wave 80%AM from 80 MHz...2 GHz

1 V/m with 1 kHz sine-wave 80%AM from 2...2.7 GHz

10 V/m with 200 Hz 50% Pulse 100%AM at 900 MHz

10 V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz

Advertising