Rockwell Automation 1799-D16U16BAGL 16 Input/16 Output Digital and 2 Input/2Output Analog  User Manual

Page 24

Advertising
background image

24 16 Input/16 Output Digital and 2 Input/2 Output Analog Embedded I/O Boards

Publication 1799-IN011A-EN-P - February 2007

10. Send the Finish Calibration command.

11. If LED indicators are no longer blinking, calibration is complete.

Calibration can be aborted or restarted at any time. Data is not saved until the end of step 10.

Example voltage calibration of channel 0.

1. Set output channel range to 0…10V.

2. Select output channel 0.

3. Apply a 10 K

Ω (± 1%) load resistor to channel 0. (10V output/10 K = 1 mA load)

4. Send Begin Calibration command.

Advertising