3. Apply a 220

Ω (±15%) load resistor to channel 0.

4. Send Begin Calibration command.

5. Send the Output Low Reference command

6. Record the actual output current.

7. Send the Output High Reference command.

8. Record the actual output current.

9. Set parameter values with recorded values.