Configuration block #1 – Rockwell Automation 5370 CVIM Communications Manual User Manual
Page 181

Appendix D
Configuration Data
D–2
Table D.1 shows the function of each word in the system environment
configuration block.
Table D.1
Configuration Block #1– System Environment
Remote I/O
& RS–232
Word #*
Bit #
Definition
Usage
Notes
0
0–15
Block Transfer Signature
1–3
0–15
Reserved
4
0–7
Configuration ID (Char. 2)
4
8–15
Configuration ID (Char. 1)
5
0–7
Configuration ID (Char. 4)
5
8–15
Configuration ID (Char. 3)
6
0–7
Configuration ID (Char. 6)
6
8–15
Configuration ID (Char. 5)
7
0–7
Configuration ID (Char. 8)
7
8–15
Configuration ID (Char. 7)
8
0–7
Configuration ID (Char. 10)
8
8–15
Configuration ID (Char. 9)
9
0–7
Configuration ID (Char. 12)
9
8–15
Configuration ID (Char. 11)
10
0–7
Configuration ID (Char. 14)
10
8–15
Configuration ID (Char. 13)
11
0–7
Configuration ID (Char. 16)
11
8–15
Configuration ID (Char. 15)
12
0–15
Reserved
13
0
Monitor Type
0 = B/W
1 = Color
13
1
Remote I/O Enable
0 = Disabled
1 = Enabled
13
2 & 4
Protocol–Port A
0 = ASCII
1 = DF1
2 = Not Specified
3 = Not Specified
Port A, see bits 5 & 6 for port B.
13
3
Host Standby Mode
0 = Standby Enabled
1 = Standby Disabled
13
5 & 6
Protocol–Port B
0 = ASCII
1 = DF1
2 = Not Specified
3 = Not Specified
Port B, see bits 2 & 4 for port A.
13
7–15
Reserved
* Refer to Chapter 6 for Pyramid Integrator long word descriptions.
Configuration Block #1