3Ć1

3.0 INSTALLATION

This section describes how to install and replace the Analog Rail

module. Note that analog signals are sensitive to variations in

temperature. The Analog Rail module is designed to perform

optimally at room temperature, approximately 25

o

C. Inall cases, the

ambient temperature of the installation must be maintained in the

range specified in Appendix A to ensure the highest possible

accuracy.

DANGER

THE USER IS RESPONSIBLE FOR CONFORMING WITH THE NATIONAL

ELECTRICAL CODE AND ALL OTHER APPLICABLE LOCAL CODES. WIRING

PRACTICES,

GROUNDING,

DISCONNECTS,

AND

OVERĆCURRENT

PROTECTION ARE OF PARTICULAR IMPORTANCE. FAILURE TO OBSERVE THIS

PRECAUTION COULD RESULT IN SEVERE BODILY INJURY OR LOSS OF LIFE.

DANGER

DO NOT TOUCH THE CONNECTORS ON THE FACEPLATE IF THERE IS POWER

ON THE WIRES ATTACHED TO THE PLUG CONNECTOR SCREW TERMINALS.

ALWAYS TURN OFF POWER BEFORE HANDLING A CONNECTOR THAT IS

WIRED. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN SEVERE

BODILY INJURY OR LOSS OF LIFE.

WARNING

UNEXPECTED OUTPUT CHANGES MAY RESULT IF AN ANALOG RAIL IS

PLUGGED INTO A LOCAL I/O HEAD THAT IS COMMUNICATING WITH A

PROCESSOR. ANY HARDWARE CONFIGURATION CHANGES MUST BE MADE

ONLY WITH THE LOCAL I/O INTERFACE CABLE (M/N 45C8) DISCONNECTED.

FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN BODILY INJURY.

CAUTION

THE ANALOG RAIL MODULE IS DESIGNED TO BE POWERED BY EITHER 24 VDC

OR 120 VAC. CONNECT THE PROPER POWER SOURCE TO THE MODULE.

FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN DAMAGE TO OR

DESTRUCTION OF THE EQUIPMENT.

3.1

Wiring

To reduce the possibility of electrical noise interfering with the

proper operation of the control system, exercise care when installing

the wiring between the module and the external hardware.
Use shielded twisted pair for all wiring between the Analog Rail

module and the external hardware. Beldent 8761 or anequivalent

cable type is recommended. For detailed recommendations refer to

IEEE 518.