Rockwell Automation 61C365 4 Output 4-20mA Analog Rail User Manual

Page 24

Advertising
background image

4Ć2

Analog Rail Module with AutoMate 20

(Local Head Mode or Rail Mode)

AutoMate 20 registers reserved for port configuration:

2734

Port 0 of AutoMate 20

2735

Port 1 of AutoMate 20

2736

Port 2 of AutoMate 20

2737

Port 3 of AutoMate 20

Local Head Mode

Enter the value 64XX for the register representing the port to which the Analog

Rail module is connected, where XX is a value from 00Ć14*. The XX value

represents the first register in a set of four contiguous registers that will be used

to store data for the port.

Rail Mode

Enter the value 16XX for the register representing the port to which the Analog

Rail module is connected, where XX is a value from 00Ć17*. The XX value

represents the register that will be used to multiplex data through the I/O port.
*Values are in octal notation.

Figure 4.1 Ć Configuration for Analog Rail Module with AutoMate 20