Rockwell Automation 61C365 4 Output 4-20mA Analog Rail User Manual

Page 30

Advertising
background image

4Ć8

4.1.3

AutoMate Programming in Local Head Mode

In Local Head mode, the module is imaged in four I/O registers of

the processor. Data from all four channels is always available and

will be updated at the end of each scan. For the output channels,

the data in the register must be in the format shown in figure 4.7

prior to the I/O update.

17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0

Octal

12 bits of analog output data
not used

not used
not used

not used

Figure 4.7 Ć Local Head Register Image for Output Channels

The Analog Rail module data may also be accessed in the middle of

the scan (as opposed to the end of the scan) using the appropriate

number of Analog Out (AOUT) blocks. See section 4.1.4 for more

information about the AOUT block.
Note that the AOUT block is supported for the AutoMate 20E

(M/N 45C224 and 45C225), but not the AutoMate 20 (M/N 45C20,

45C21, 45C220, 45C221) by APX Version 3.0.
For processors that do not support the AOUT block, you can use

the MOVE block to move data in and out of the registers assigned.

The I/O update will occur automatically at the end of each scan. See

Appendix C for a sample AutoMate program that writes to the

Analog Rail module without using AOUT block.

4.1.4

Analog Out (AOUT) Instruction Block

The AOUT block is used to write outputs to the Analog Rail module.

AOUT blocks are supported for the 20E processor. The AOUT block

makes it possible to update the channels on the Analog Rail module

during the scan instead of at the end of the scan (the standard

AutoMate I/O update). The block also makes it possible to update all

four channels during the scan in Rail mode, a hardware

configuration which would otherwise allow only one channel on the

module to be updated. The format of the block is shown in

figure 4.8.