4Ć9

AOUT Instruction Block

The example below shows an AOUT block for an Analog Rail module connected

to port 2 of a local I/O head, which in turn is connected to port 3 of an AutoMate

Processor. Data from register 2000 is used in this example.

SRC Ć

Register number from which the data to output will be taken.

IOPORT Ć Processor port to which the Analog Rail is connected (directly or

indirectly); value range 0Ć3.

LHPORT Ć Local I/O Head port to which the Analog Rail is connected; value

range 0Ć3. If a Local I/O Head is not used, the value is 0.

CHAN Ć

Channel on the Analog Rail module to write; value range 0 or 1.

12

.01

AOUT

[ ]

EN

EN

ER

AOUT

AutoMate 20E

with ports

0, 1, 2, and 3

Analog Rail with

channels 0, 1, 2, and 3

In Rail Mode

0

1

2

3

Chan 0

Chan 1

Chan 2

Chan 3

13

.01

( )

76

.00

( )

SRC:

VALUE:

IOPORT:

LHPORT:

CHAN:

2000
3

2

1

Local Head

with ports

0, 1, 2, and 3

0

1

2

3

Figure 4.8 Ć AOUT Instruction Block

4.2

Analog Rail Module in DCS 5000/AutoMax

Systems

This section describes how the Analog Rail is used with

DCS 5000/AutoMax systems.

4.2.1

Configuring the Analog Rail Module with a

DCS 5000/AutoMax Remote I/O Head

The Analog Rail module is used in the Local Head mode when the

host is a DCS 5000/AutoMax Remote I/O Head. For AutoMax

Version 3.0 and later, the Analog Rail module is configured using the

AutoMax Programming Executive. Refer to instruction manual

JĆ3750 for more information. For DCS 5000 or AutoMax Version 2.1

or earlier, the module is defined in the configuration task for the

master rack using the DCS 5000 or AutoMax Programming

Executive software. See instruction manual JĆ3649 for more

information on the configuration task.