3 module replacement – Rockwell Automation 61C365 4 Output 4-20mA Analog Rail User Manual

Page 20

Advertising
background image

3Ć6

Step 16. Verify that the hardware has been installed correctly.

Before testing, insure that the external hardware will not

respond to output signals from the Analog Rail module.

WARNING

BE CAREFUL WHEN WRITING TO THE OUTPUTS TO INSURE THAT NO

UNEXPECTED MACHINE MOTION WILL RESULT. FAILURE TO OBSERVE THIS

PRECAUTION COULD RESULT IN BODILY INJURY OR DAMAGE TO EQUIPMENT.

For AutoMate systems, you must configure the AutoMate

processor using the AutoMate Programming Executive

(APX) before testing. See section 4.0 for more

information. After configuring the module, use the APX

Point Monitor function to test the module. You can test the

Analog Rail module output channels by writing a value

between 0 and 4095 to those channels and, with an

ammeter, verifying that the output on the terminal points

(4Ć20mA) is proportional.
For DCS 5000, AutoMax, or Distributed Power DĆC Drive

systems, use the DCS 5000 or AutoMax Programming

Executive software I/O Monitor function, respectively. Test

output channels by writing a value between 0 and 4095 to

those channels and using an ammeter to verify that the

signal on the terminal points (4Ć20mA) is proportional.

3.3

Module Replacement

Use the following procedure to replace the module.
Step 1.

Stop any application programs that are running.

Step 2.

Turn off power to the external hardware connected to the

output channels on the faceplate of the module.

Step 3.

Turn off power to the Analog Rail module (120 VAC or

24 VDC).

Step 4.

Turn off power to the Reliance device connected to the

Analog Rail module.

Step 5.

Disconnect the I/O Rail cable from the Analog Rail

module.

Step 6.

Without disconnecting the wiring, remove the 12Ćpoint

terminal from the faceplate and set aside.

Step 7.

Without disconnecting the wiring, remove the 4Ćpoint

terminal from the faceplate and set aside. Disconnect the

ground wire from the bottom of the rightĆhand flange.

Step 8.

Loosen the screws that hold the Analog Rail module to

the panel and remove the module.

Step 9.

If the power supply you are using is 24 VDC, you need to

replace the factoryĆinstalled .25A fuse in the new module

with the .75A fuse that came in the shipping box with the

module. Use a screwdriver to release the fuse holder

located on the Analog Rail module faceplate. Pull the fuse

holder out of the module.

Advertising