4Ć7

4.1.2

AutoMate Programming in Rail Mode

In Rail mode, the Analog Rail module is imaged in one I/O register of

the processor. Data from one of the four channels will occupy the

register as a function of the channel select bits. The active channel

is updated at the end of each scan. For the output channels, the

data in the register must be in the format shown in figure 4.6 prior to

the I/O update.

17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0

Octal

12 bits of analog output data
not used

not used
channel being modified: LSB
channel being modified: MSB

MSB LSB ăCH#

ă0ąą0 = CH 0

ă0ąą1 = CH 1

ă1ąą0 = CH 2

ă1ąą1 = CH 3

Figure 4.6 Ć Rail Mode Register Image for Output Channels

The Analog Rail module data may also be accessed in the middle of

the scan (as opposed to the end of the scan, which is the normal

mode of operation for digital rail I/O) using the appropriate number

of Analog Out (AOUT) blocks. The AOUT block will set the channel

select bits appropriately. See section 4.1.4 for more information

about the AOUT block.
Note that the AOUT block is supported for the AutoMate 20E

M/N 45C224 and 45C225, but not the AutoMate 20 (M/N 45C20,

45C21, 45C220, 45C221) by APX Version 3.0.
For processors that do not support the AOUT block, you can use

the MOVE block to move data in and out of the registers assigned

and to determine the channel select bits. The I/O update will occur

automatically at the end of each scan. See Appendix C for a sample

AutoMate program that writes to the Analog Rail module without

using AOUT blocks.