Initial Installation
Use the following procedure to install the Analog Rail module.
Step 1.
Using the mounting dimensions shown in figure 3.1,
prepare the necessary mounting provisions on the panel.
The module is designed to be mounted vertically using
four #10 or M5 bolts or studs. Multiple modules should
be mounted side by side. The flange width of two
modules side by side is sufficient to dissipate the heat
produced by the modules. The modules can also be
mounted one above the other, but since this hardware
configuration does not allow the most efficient heat
dissipation, the minimum clearance between the module
chassis is 3". See figure 3.1.
7.0"
9.25"
Depth: 7.75"
Diameter of mounting holes: 7/32"
2.44"
3.0"
2.94"
Figure 3.1 Ć Mounting Dimensions