A technical specifications, Appendix a, Technical specifications – Rockwell Automation 61C365 4 Output 4-20mA Analog Rail User Manual

Page 37

Advertising
background image

AĆ1

Appendix A

Technical Specifications

Ambient Conditions

D Storage temperature: -40_C to 85_C

-40_F to 185_F

D Operating temperature (at the module): 0_C to 60_C

32_F to 140_F

D Humidity: 5Ć90% nonĆcondensing

Dimensions

D Height: 9.25 inches (23.5 cm)
D Width: 2.94 inchesă(7.5 cm)
D Depth: 7.75 inches (19.7 cm including plugĆin terminals)
D Weight: 4.5 lbsă(2.1 kg)

Recommended Cable for Analog Signal Wiring

D Belden 8761 or equivalent type

Maximum Power Dissipation

D 4.5 Watts

Communication Power Requirements

D +5V: 250 mA (supplied by host through I/O Rail cable)

Analog Circuit Power Supply

(use either 120 VAC or 24 VDC supply)
D 120 VAC supply: 92 Ć 132V acceptable range (+15% /-20%)

Maximum current: 150mA

D 24 VDC supply: 20 Ć 32V acceptable range (+33%/-16%)

Maximum current: 350mA

Maximum Source KVA

D 10

Fuse Types and Rating

D MDQ 250 VAC .25A (for 120 VAC power)
D MDQ 250 VAC .75A (for 24 VDC power)

Advertising