For DCS 5000 or AutoMax Version 2.1 or earlier, use the RIODEF
statement to define each channel on the Analog Rail module as a
separate register. Use the following format for the RIODEF
statement:
nnnnn RIODEF name[MASTER_SLOT=m, DROP=d, SLOT=s, REGISTER=r, BIT=b]
where:
nnnnn Ć Configuration task line number; range 1Ć32767.
name Ć Symbolic name of channel, ending with % (integer) for
registers, @ (booleans) for bits.
m
Ć Slot in rack containing DCS 5000/AutoMax master remote
I/Omodule; range 0Ć15.
d
Ć Drop number of DCS 5000/AutoMax Remote I/OHead;
range 1Ć7.
s
Ć Communication port on the DCS 5000/AutoMax Remote
I/OHead to which the Analog Rail module is connected;
range 0Ć3.
r
Ć Register number; range 0Ć3.
b
Ć Optional field defining the bit position within the register
number; range 0Ć15.
4.2.2
Configuring the Analog Rail Module with a Power
Module Interface Processor Host
The Analog Rail module is used in the Rail mode when the host is a
Power Module Interface (PMI) Processor. Beginning with AutoMax
Version 3.3, the Analog Rail module is configured using the AutoMax
Programming Executive. Refer to instruction manual J2Ć3045 for
more information.