Rockwell Automation 61C365 4 Output 4-20mA Analog Rail User Manual

Page 32

Advertising
background image

4Ć10

For DCS 5000 or AutoMax Version 2.1 or earlier, use the RIODEF

statement to define each channel on the Analog Rail module as a

separate register. Use the following format for the RIODEF

statement:

nnnnn RIODEF name[MASTER_SLOT=m, DROP=d, SLOT=s, REGISTER=r, BIT=b]

where:
nnnnn Ć Configuration task line number; range 1Ć32767.
name Ć Symbolic name of channel, ending with % (integer) for

registers, @ (booleans) for bits.

m

Ć Slot in rack containing DCS 5000/AutoMax master remote

I/Omodule; range 0Ć15.

d

Ć Drop number of DCS 5000/AutoMax Remote I/OHead;

range 1Ć7.

s

Ć Communication port on the DCS 5000/AutoMax Remote

I/OHead to which the Analog Rail module is connected;

range 0Ć3.

r

Ć Register number; range 0Ć3.

b

Ć Optional field defining the bit position within the register

number; range 0Ć15.

4.2.2

Configuring the Analog Rail Module with a Power

Module Interface Processor Host

The Analog Rail module is used in the Rail mode when the host is a

Power Module Interface (PMI) Processor. Beginning with AutoMax

Version 3.3, the Analog Rail module is configured using the AutoMax

Programming Executive. Refer to instruction manual J2Ć3045 for

more information.