39 writevar% function – Rockwell Automation 57C610 Enhanced Basic Language, AutoMax User Manual

Page 106

Advertising
background image

7Ć18

Values Returned:
ă1

Success

-22 Variable not found

-23 Data type mismatch
For example:

VARIABLE_NAME$ = SET_POINTS(17)"
STATUS% = READVAR%( VARIABLE_NAME$, VALUE )

7.39

WRITEVAR% Function

This function requires the AutoMax operating system with the

Ethernet option.
Format:

WRITEVAR%( vn$, value )

where:

vn$

is a string expression for the name of the variable to

write to. It can be a boolean, integer, double integer,

real, or an array of these types. Only single

dimension arrays are allowed.

value

is the variable that has the value to write.

This function accepts a variable name as a string expression and a

value to write into the variable. The string that defines the variable

name must have a suffix as follows:
@

Booleans

%

Integers

!

Double integers

No suffix

Reals

If specifying an array element, the subscript must be after the data

type character if there is one.
If the data type of the variable, as defined in the string vn$, is

different than that of VALUE, an error is generated. Only common

variables can be accessed.
Values Returned:
ă1 Success

-22 Variable not found

-23 Data type mismatch

-24 Variable forced
For example:

VARIABLE_NAME$ = SET_POINTS(17)"
VALUE = 12.345
STATUS% = WRITEVAR%( VARIABLE_NAME$, VALUE )