Rockwell Automation 2500 CENTERLINE MCC Joining and Splicing Columns User Manual

Page 11

Advertising
background image

Publication 2500-IN004A-EN-P - August 2009

CENTERLINE 2500 Motor Control Centers Installing, Joining and Splicing Columns 11

4. Slide the columns together making sure cabinets are level and

joining holes are aligned.

5. If lifting angles are removed from IP54 enclosures, you must seal

the lifting angle bolt holes with the caulking sealer.

6. For Front-only Configured Single Column Shipping Blocks,

remove the bottom horizontal wireway cover to fasten the front
of the MCC to the foundation.

If rear access is available, remove the back plate and fasten the
rear of the MCC to the foundation as illustrated in

Preferred

Mounting Arrangement

. If rear access is not available, fasten the

first column to the foundation before moving adjacent columns
into place.

Preferred Mounting Arrangement

7. For Front-only Configured Two Column Shipping Blocks,

remove the bottom horizontal wireway cover to fasten the front
of the MCC to the foundation.

700,0

(27.56)

642,0

(25.28)

561,0

(22.09)

69,0

(2.72)

29,0

(1.14)

82,0

(3.23)

18,0

(0.71)

600,0 - 800,0

(23.62 - 31.50)

44,0

(1.73)

513,0 - 713,0

(20.20 - 28.07)

438,0 - 638,0

(17.24 - 25.12)

234,0

(9.2)

6,0

(0.24)

Front-only Configured, Single Column
Shipping Blocks

Dimensions are in mm and (in.)

Diagram illustrates 600,0 and 800,0 mm
(23.62 and 31.50 in.) column depth

Protective Earth
Conductor

Front

(4) Mounting
Holes