Rockwell Automation 2500 CENTERLINE MCC Joining and Splicing Columns User Manual

Page 19

Advertising
background image

Publication 2500-IN004A-EN-P - August 2009

CENTERLINE 2500 Motor Control Centers Installing, Joining and Splicing Columns 19

Splicing Power Bus, 800…4000 A

Follow these procedures to splice the power bus.

1. Assemble splice bars and hardware as shown in illustrations on

pages

19

through

21

.

Repeat for each phase of busbar and, if present, the neutral bar.

2. Tighten hardware to torque specifications.

See

Torque Requirements for Hardware Connections

on

page 23

.

Do not grease or lubricate hardware.

3. Replace the horizontal bus access covers and check that the

bolts and nuts are secure.

4. Replace the units and unit support pans in their respective

stations if they were removed.

Power Bus Splicing Configuration, 800…1250 A