CENTERLINE 2500 Motor Control Centers Installing, Joining and Splicing Columns 15

11. For 800 mm Deep Columns, first complete step 9; then, working

from the left, use the M6 hex head bolt, lock washer and nut
hardware provided in the power bus splice kit to fasten the two
additional joining holes together.

Ensure cabinets are tightly pushed together.

Joining Hole Locations 800 mm Deep

Refer to

Torque Requirements for Hardware Connections

on

page 23

for torque requirements.

12. Inspect the interior for dust and dirt.

Vacuum cleaning is recommended.

IMPORTANT

Do not use hardware to draw cabinets together.

IMPORTANT

Do not clean using compressed air. It may contain moisture and may
blow debris into the control equipment.