ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 17

Publication

1797-5.15 - June 2010

Certified Equivalent ControlNet Ex System Diagram Items

You may use these items as equivalents for the items shown on the system
diagram.

Certification Specific ControlNet Ex System Diagrams

The following pages include certification specific ControlNet Ex system
diagrams and notes pertaining to these diagrams. Select either CENELEC,
UL, C-UL, or FM and follow the requirements of that diagram as you
configure and install your system.

System Diagram Name

Catalog Number

Source

1797-RPA

1797-RPA

Allen-Bradley

1797-RPFM

1797-RPFM

Allen-Bradley

1797-ACNR15

1797-ACNR15

Allen-Bradley

Coax Trunk Cable

(1)

1786-RG6

Allen-Bradley

3092A

(2)

Belden Wire & Cable Co.

3092A with blue jacket

Belden Wire & Cable Co.

ControlNet Ex Tap

1797-TPx

Allen-Bradley

CNet Ex Trk Trm

1797-XT

Allen-Bradley

CNet Ex Tap Trm

1797-TCAP

Allen-Bradley

1

In addition to these cable types, the following specification can be followed to allow additional
types:

Cable Impedance = 75

 + 3 

Cable Capacitance = <5.94 nF per 100 m

Cable Resistance = >9.08

 per 100 m

Cable Attenuation

0.2 MHz > 0.93 dB/100 m

5 MHz > 1.39 dB/100 m

(-20…70 °C)

0.5 MHz > 0.95 dB/100 m

10 MHz > 1.86 dB/100 m

1 MHz > 1.07 dB/100 m

20 MHz > 2.73 dB/100 m

2 MHz > 1.16 dB/100 m

50 MHz > 4.33 dB/100 m

2

Belden Wire & Cable 1189A may be used, but with functional loss of communication distance,
nodes, or both.