Rockwell Automation 1797-RPFM ControlNet Ex Modular Repeater Adapter Fiber Repeater Module User Manual

Page 23

Advertising
background image

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 23

Publication

1797-5.15 - June 2010

FM ControlNet Ex Requirements



The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a
system when the approved values of V

oc

and I

sc

or V

t

and I

t

of the associated

apparatus are less than or equal to V

max

and I

max

of the intrinsically safe

apparatus and the approved values of C

a

and L

a

of the associated apparatus

are greater than C

i

+ C

cable

and L

i

+ L

cable

respectively for the intrinsically safe

apparatus.



Wiring methods must be in accordance with the National Electric Code,

ANSI/NFPA 70, Article 504 and 505. For additional information refer to
ANSI/ISA RP12.6.



WARNING: Substitution of components may impair intrinsic safety.



If fiber optic cable is provided with a metal shield, it must be connected

to a dedicated intrinsic safety ground in the nonhazardous location and tied
back in the hazardous location or be connected to a ground in the hazardous
location and tied back in the nonhazardous location.



The glass fiber must have a minimum diameter of 6 m.



The ControlNet Ex tap must be connected directly to the module (no

additional cable may be connected).



Must be FM approved.



Total coax trunk cable length is limited to 1000 m (3280 ft) with up to 2

ControlNet Ex taps connected and to 250 m (820 ft) with the maximum
allowed ControlNet Ex taps of 48. For ControlNet Ex taps between 2 and 48
use: 1000 m (3280 ft) - 16.3 m (53.4 ft) x (number of taps - 2) to find the
maximum allowed cable length.