Module Indicators

The following explains the indications seen on the 1797-RPA and
1797-RPFM modules.

1797-RPA Indicators

The figure below identifies indicators on the repeater adapter.

Power Indicator

Comm and Module Status Indicators for the 1797-RPA Module

If

This Indicates

Steady Green

Power is applied.

Off

No power is applied.

If Both Are

This Indicates

Alternately

Red/Green

The adapter is being powered-up or reset. The LEDs alternately
flash red and green for about 5 s.

Steady Green

Normal operation.

Off

The unit is not powered. Check the module power status.

Red

There is an adapter fault.
If the fault indication is caused by a jabber condition, the fault
indication will automatically be cleared when the jabber condition
is removed from the coax or fiber port.
If a jabber condition is not causing the fault, replace the repeater
adapter.